分类导航: 工业控制类 >> 人机界面

Functional Specification
Class |
H Class |
International Safety Standards |
 |
Display Type |
Monochrome LCD |
Display Colors |
Black and White(16 Shades) |
Backlight |
White LED (When replacement is required, contact your local GP distributor) |
Display Resolution |
320 x 240 pixels (QVGA) |
Effective Display Area |
117.2mm x 88.4mm |
Brightness Control |
16 levels of adjustment available via touch panel |
Contrast Adjustment |
8 levels of adjustment available via touch panel |
Language Fonts |
Japanese: 6962 (JIS Standards 1&2)(including 607 non-kanji characters), ANK: 158 (Korean fonts, Simplified and traditional Chinese fonts are downloadable.) |
Text Composition |
Character Sizes |
Standard font: 8 x 8, 8 x 16, 16 x 16 and 32 x 32 dot fonts, Stroke font: 6 to 127 dot fonts |
Font Sizes |
Standard font: Width can be expanded up to 8 times. Height can be expanded up to 8 times *2 |
Text |
8 x 8 dots |
40 Char. x 30 rows |
8 x 16 dots |
40 Char. x 15 rows |
16 x 16 dots |
20 Char. x 15 rows |
32 x 32 dots |
10 Char. x 7 rows |
Memory |
Application |
8MB FLASH EPROM *3 |
Data Backup |
320KB SRAM *4 |
Touch Panel |
Type |
Resistive Film (analog) |
Resolution |
1024 x 1024 |
Control Memory |
Variable Area |
64 KB SRAM (uses lithium battery) *4 |
Program Area |
- *5 |
Number of Step |
- |
Function Switch |
12 switches (Right: 6 switches, left: 6 switches)(DOUT:2 Open collector output [F1,F2], Operation switch:I open collector output [O.P]) *6 |
Emergency Switch Output Interface |
Push-lock switch 3 contacts (a-contact: 1 contact, b-contact: 2 contacts) Rated voltage: DC30V Maximum rated current: 1 A (Minimum allowable load: DC5V, 1 mA)Applicable standards *7 ICE60947-5-1, EN60947-5-1, ICE60947-5-5, EN60947-5-5,UL508, CSA C22.2 No.14 |
3-Position Enable Switch Output Interface |
GP Rear panel switch 2 contacts (b-contact) Rated voltage: DC30V Maximum rated current: 700mA (Minimum allowable load: DC3V, 5 mA) Applicable standards *7 ICE/EN60947-5-1, ICE/EN60947-5-8, UL508 (UL approval), CSA C22.2 No.14 (UL approval), ISO12100/EN292, IEC60204-1/EN60204-1, ISO11161/prEN11161, ISO10218/EN775, ANSI/RIA R15.06, ANSI B11.19 |
Key Switch Output Interface |
1c-contact Rated voltage: DC24V Maximum rated current: 300 mA |
Interface |
Serial (COM1) *8 |
Asynchronous Transmission: RS-232C/422/485 Data Length: 7/8 bits, Stop Bit: 1/2 bits, Parity: none, Odd or Even, Data transmission speed: 2400bps to 115.2kbps 187.5kbps(MPI) *9, Connector: D-Sub 9pin socket |
USB |
USB1.1 (USB TYPE-A conn.) x 1 |
CF Card |
CF Card Slot (TYPE-II) x 1 |
External Output I/F |
DOUT Output |
Open Collector Output: 2 points (F1, F2) Rated Voltage: DC24V Rated Current: 300 mA/point max. *6 |
Operation Output |
Open Collector Output: 1 point Rated Voltage: DC24V Rated Current: 300 mA max. *6 |
External Buzzer Output |
Open Collector Output 1 point Rated Voltage: DC24V Rated Current: 300 mA max. *6 |
General Specification
Ship Standard Acquisition |
- |
Input Voltage |
DC24V |
Rated Frequency |
- |
Rated Voltage |
DC19.2V to DC28.8V |
Allowable Voltage |
10ms or less |
Power Consumption |
16.7W or less |
Voltage Endurance |
AC500V 20mA for 1 minute(between charging and FG terminals) |
Insulation Resistance |
10MΩ or higher at DC500V (min.)(between charging and FG terminals) |
Surrounding Air Temperature |
0oC to +40oC *10 |
Storage Temperature |
-20oC to +60oC |
Humidity |
10%RH to 90%RH (Non-condensing, wet bulb temperature: 39oC max.) |
Storage Humidity |
10%RH to 90%RH (Non-condensing, wet bulb temperature: 39oC max.) |
Pollution Degree |
Pollution Degree 2 |
Atmosphere |
Free of corrosive gasses |
Air Pressure Vibration Resistance (Availment altitude) |
800hPa to 1114hPa (2000 meters or lower) |
Vibration Resistance |
IEC61131-2 compliant 5Hz to 9Hz Single-amplitude 3.5mm 9Hz to 150Hz Fixed acceleration 9.8m/s2 X,Y,Z directions for 10 cycle (100min.) |
Noise Immunity (via noise simulator) |
Noise Voltage: 1000Vp-p Pulse Duration: 1μs Rise Time: 1ns |
Electrostatic Discharge Immunity |
6kV (complies with EN 61000-4-2 Level 3) |
Grounding |
100Ω or less, or your country's applicable standard *11 |
Ratings (For front panel of installed unit) |
Equivalent to IP65f NEMA #250 TYPE 4X/13 *12 |
External Dimensions |
W224mm x H174mm x D87.1mm |
Weight |
1.0kg max.(Unit Only) |
Cooling Method |
Natural air circulation |
*1 |
Changing the Colors setting to "65,536 colors" will disable the blinking feature on all screens in your project. If you wish to use the blinking feature, select "16,384 colors". |
*2 |
Font Sizes can be set up by software. |
*3 |
User area. |
*4 |
A Lithium battery's lifetime is: 10 years when the battery's ambient temperature is 40oC or less. 4.1 years when the battery's ambient temperature is 50oC or less. 1.5 years when the battery's ambient temperature is 60oC or less. When used for back up: Approximately 60 days, with a fully charged battery. Approximately 6 days, with a half-charged battery. |
*5 |
Logic Programming is not available. |
*6 |
In using DOUT, Operation Switch and Eternal Output I/F, the exclusive cable and conversion adapter are necessary. |
*7 |
The specification of whole system may not be fulfilled by usage environment. Please design with understanding the specification correctly. |
*8 |
GP3000H cable (without connector) or GP3000H cable (with connector) with conversion adapter is necessary. |
*9 |
RS-232C and RS-422/485 are software switchable. |
*10 |
When using STN Color LCD models in an environment where the temperature becomes or exceeds 40oC for an extended period of time, the screen contrast level may decrease from its original level of brightness. Operating temperature refers to temperature inside mounting enclosure. |
*11 |
Grounding requirements differ from country to country. Be sure to confirm your work environment requirements prior to installation. For more information, please contact your local Pro-face office. |
*12 |
The degree of protection provided by these products is equivalent to IP65f, however their performance cannot be guaranteed for every environment. Be sure to confirm your work environment requirements prior to installation. |
External Dimensions, Parts Names
Adapter
|